Ventilation

ASHRAE 170

ANSI/ASHRAE/ASHE Standard 170 — Ventilation of Health Care Facilities

ASHRAELatest · 2021 (with addenda)Referenced by FGI Guidelines and by CDC infection-control guidance.

Scope

Standard 170 specifies minimum ventilation requirements for hospital, outpatient, and residential health-care spaces. It defines air changes per hour (ACH), pressure relationships, filtration efficiency, and temperature/humidity ranges for every functional space in a hospital, including the patient room and airborne infection isolation room.

Where it applies in the room

  • Total and outdoor air changes per hour by room type
  • Pressure relationship (positive, negative, neutral) versus adjacent spaces
  • Filtration MERV / HEPA requirements
  • Temperature and relative humidity ranges

Key requirements at a glance

Med-surg room6 total ACH, of which 2 are outdoor; pressure neutral to corridor.
ICU room6 total ACH, of which 2 outdoor; pressure neutral to corridor.
AIIR (isolation)≥ 12 ACH new / ≥ 6 existing; negative to corridor by ≥ 0.01 in. w.c.
Protective environment room≥ 12 ACH; positive to corridor; HEPA-filtered supply.

Summarized for reference. Consult the source document for the definitive text.