ANSI/ASHRAE/ASHE Standard 170 — Ventilation of Health Care Facilities
Scope
Standard 170 specifies minimum ventilation requirements for hospital, outpatient, and residential health-care spaces. It defines air changes per hour (ACH), pressure relationships, filtration efficiency, and temperature/humidity ranges for every functional space in a hospital, including the patient room and airborne infection isolation room.
Where it applies in the room
- Total and outdoor air changes per hour by room type
- Pressure relationship (positive, negative, neutral) versus adjacent spaces
- Filtration MERV / HEPA requirements
- Temperature and relative humidity ranges
Key requirements at a glance
| Med-surg room | 6 total ACH, of which 2 are outdoor; pressure neutral to corridor. |
|---|---|
| ICU room | 6 total ACH, of which 2 outdoor; pressure neutral to corridor. |
| AIIR (isolation) | ≥ 12 ACH new / ≥ 6 existing; negative to corridor by ≥ 0.01 in. w.c. |
| Protective environment room | ≥ 12 ACH; positive to corridor; HEPA-filtered supply. |
Summarized for reference. Consult the source document for the definitive text.
Source & further reading
- · ASHRAE Standard 170 — publisher page — publisher
- · ANSI/ASHRAE/ASHE 170-2021 (Techstreet listing) — official edition
Also known as
- ANSI/ASHRAE/ASHE Standard 170
- ASHRAE Standard 170
- ASHRAE 170
Help us improve
Spotted something wrong, outdated, or unclear? Let the editors know.
Cited in
Guides that reference ASHRAE 170
What Happens Inside an ICU Room
The equipment, people, and information flows in a modern intensive care unit — mapped end to end.
Negative Pressure Rooms
The airflow engineering that keeps infectious pathogens contained.
Isolation Rooms
Contact, droplet, and airborne precautions — and how each shapes the room.